Keyword: Engineering and Technology, Electrical Engineering, Electronic Engineering, Information Engineering, Other Electrical Engineering, Electronic Engineering, Information Engineering, Teknik och teknologier, Elektroteknik och elektronik, Annan elektroteknik och elektronik, Electric Power Engineering, Elkraftteknik
Publication year: 2019
Relevant Sustainable Development Goals (SDGs):
SDG 9 Industry, innovation and infrastructure
The SDG label(s) above have been assigned by OSDG.ai

Abstract:

This paper presents levels of harmonic voltage distortion with low-voltage customers during 2017 and 2018. Measurements were obtained over a period between one hour and one day per location. Results are presented for the harmonics in the phase-to-neutral voltage at 163 locations; the highest 10-minute values per location have been used for presenting the results. For harmonics in the neutral-to-ground voltage, 1-second values at 88 locations have been used. The harmonic levels showed to be well below the limits in EN 50160 and IEC 61000-2-2 for almost all locations and for all harmonics with exception of harmonics 9, 15 and 21. The dominating frequencies at most locations are harmonics 5 and 7.