Long-term power quality measurements in medium voltage networks

Document identifier: oai:DiVA.org:ltu-76892
Access full text here:10.34890/197
Keyword: Engineering and Technology, Electrical Engineering, Electronic Engineering, Information Engineering, Other Electrical Engineering, Electronic Engineering, Information Engineering, Teknik och teknologier, Elektroteknik och elektronik, Annan elektroteknik och elektronik, Electric Power Engineering, Elkraftteknik
Publication year: 2019
Abstract:

A power quality survey has been performed in several Swedish medium voltage (MV) substations and a study of the long-term power quality levels under normal operation has been done. The measurements have been performed during several years and the study includes seasonal variations as well as weekly and daily variations. This paper will focus on harmonic voltage distortion (THD and individual harmonics). An analysis has been done looking into metrological data to see any possible correlation with variations in harmonic distortion. Conclusions show that there are some significant differences over the years and between days for all sites. Long term measurements are needed to gain information on which levels one can expect, measuring for only a few weeks or month can give an over or underestimation of the actual levels. Results also shows that the magnitudes of harmonic distortion are well below the permitted level at all time at the selected sites.

Authors

Sarah Rönnberg

Luleå tekniska universitet; Energivetenskap
Other publications >>

Elena Gutierrez Ballesteros

University of Cordoba, Spain
Other publications >>

Aurora Gil de Castro

University of Cordoba, Spain
Other publications >>

Malin Westman

Skellefteå Kraft Elnät, Sweden
Other publications >>

Magnus Brodin

Skellefteå Kraft Elnät, Sweden
Other publications >>